1) Check the switch, switch position is correct, interlock switch in line with the mode of operation requirements.
2) check the insurance installed on the good, the power supply is normal.
3) Check the 24V battery voltage is normal, the charger is operating normally.
4) No oil leakage in the diesel generator, the oil level of the diesel generator is normal and the oil valve is open.
5) diesel generator outlet control switch in any case shall not be manually operated.
6) After the diesel generator starts and stops, it will reset the self-starting screen reset button once.
7) Diesel generator operation period, it was at the scene to monitor the operation of diesel generators, in line with regulatory requirements.
8) 400V factory bus when power failure, diesel generators, such as not since the start, allowing manual start time, but each time the start time of not more than 15 seconds.
9) 400V bus power plant loss of electricity, diesel generators start normally, if the diesel generator to the security section of the power switch is not closed, after the confirmation of the power supply sub-gate should grab once.
10) diesel generator fire extinguishing equipment should be complete.